Finding Conduit Size —
Multiple Conductors, Different Wire Sizes and Types
Three 1/0 THWN 75°C conductors and one #2 XHHW 75°C Copper
conductor are to connect to a panel board using a single Conduit.
What is the cross-sectional area of Wires, Conduit Size and actual
ll Area?
Note: The cross-sectional Areas are the same for both THHN and
THWN; display will show as THHN.
KEYSTROKE DISPLAY

0.
1. Set to 75º C:
(
75º
)
75 0.
2. Set to Copper (if necessary):
(
Cu/Al
)
75 Cu 0.
3. Enter Conduit Type:

(Cond Type
)
FMC nonE COND
4. Enter rst Wire Size:
*
AWG 0 CU WIRE SIZE
5. Enter number of THWN Wires:

THHN 3. WIRES
6. Find cross-section Wire Area:
THHN 0.5565 WIRE AREA
7. Enter second Wire Size:
*
AWG 2 CU WIRE SIZE
8. Enter number of XHHW Wires:

XHHW 1. WIRE
9. Find cross-sectional Wire Area:
XHHW 0.1146 WIRE AREA