
User's GUide — 31
Wire Sizing Based on Insulation Rating
Wiring is being installed in a 240 Volt, Single-Phase system rated at
30 kVA. What is the Wire Size needed if you use 60° C Copper wire?
KEYSTROKE DISPLAY
0.
1. Set to 1-Phase:
(1Ø)
1 Ø 1 PH
2. Set to 60º C:
(60º)
1 Ø 60 1 PH
3. Set to Copper (if necessary):
(Cu/Al)
1 Ø 60 Cu 1 PH
4. Enter kVA:
KVA 30.
5. Enter Volts:
VOLT 240.
6. Find Amps:
AMPS 125.
7. Find Wire Size:
AWG 0 CU WIRE SIZE
8. Display Wire Ampacity:
Ø* 125.0 WIRE A
* The Wire Size will be shown in the upper left area of the display when
displaying the Wire Ampacity rating.
9. Display CMIL:
CMIL 105,600. WIRE
10. Display NEC Table:
NEC 310.15.b.16
Comentarios a estos manuales