Calculated-industries 5070-A User Guide Manual de usuario Pagina 30

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 66
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 29
User's GUide — 29
(cont’d)
KEYSTROKE DISPLAY
5. Enter HP:

IND* 10. HP
* If IND is not shown, press until IND is displayed in the upper left
area of the display.
6. Find Full-Load Current:
FLC 28. A
7. Find 125% Ampacity Wire Size:
(125%)
AWG 8 CU WIRE SIZE 125%
8. Find max Ampacity:
8* 40.0 WIRE A125%
* The Wire Size will be shown in the upper left area of the display when
displaying the Wire Ampacity rating.
Finding Synchronous Motor Horsepower
A Synchronous motor is dened as having a 27 Amp load on a 240
Volt, 3Ø circuit. What is its Horsepower?
KEYSTROKE DISPLAY

0.
1. Set to 3-Phase:
(3Ø)
3 PH
2. Set to Synchronous motor:
*(Ind/Sync/DC)
SYNC 0.
* If necessary, continue pressing until the desired Motor Type
is displayed.
3. Enter Volts:

VOLT 240.
4. Enter Amps:

AMPS 27.
Vista de pagina 29