User's GUide — 25
1. Set to 1-Phase:
(1Ø)
1 Ø 1 PH
2. Enter Volts:

VOLT 120.
3. Set Power Factor:
(PF%)
PF% 87.
4. Enter Amps:

AMPS 45.
5. Solve for Watts:
WATT 4,698.
Finding kW Rating
What’s the kW rating for a 90 Amp, 208 Volt, Three-Phase boiler with
100% Power Factor?
KEYSTROKE DISPLAY
0.
1. Set to 3-Phase:
(3Ø)
3 PH
2. Set Power Factor:
 (PF%)
PF% 100.
3. Enter Amps:

AMPS 90.
4. Enter Volts:

VOLT 208.
5. Solve for kW:

KW 32.423991
KEYSTROKE DISPLAY